Fujitsu SET-ARTH60KHTB 16.0kW High Static R32 Ducted AC System 1 Phase (High Performance)

Fujitsu SET-ARTH60KHTB 16.0kW High Static R32 Ducted AC System 1 Phase (High Performance)

Regular price $6,245.00 AUD
Regular price Sale price $6,245.00 AUD
Sale Sold out

FREE PICKUP ACROSS AUSTRALIA! Contact us now for details

16.0kW Cooling
18.0 kW Heating

Fujitsu SET-ARTH60KHTB 16kW High Static R32 Ducted AC System 1 Phase (High Performance)
Includes Indoor Unit: ARTH60KHTB / Outdoor Unit : AOTH60KCTA
Wired Remote Controller : UTY-RNRT – Backlit Touch Panel Wall Controller

The High Static R32 ducted models are up to 19.7 per cent more energy efficient across the range compared to previous models. The High Static R32 ducted range features the same lightweight and compact indoor unit chassis design to enable the continuation of installation ease and flexibility.

Specifications:



Indoor unit ARTH60KHTB
Outdoor unit AOTH60KCTA
Operation Type Reverse Cycle
Power Source
V/Ph/Hz
230 / 1 / 50
Cooling Capacity
kW (Rated (Min – Max))
16.00 (7.4 – 17.5)
Heating Capacity
kW (Rated (Min – Max))
18.00 (7.4 – 20.5)
Input Power Cooling
kW (Rated (Max))
4.82 (5.31)
Input Power Heating
kW (Rated (Max))
4.63 (5.19)
EER Cooling
kW/kW
3.32
COP Heating
kW/kW
3.89
Star Rating Cooling
(0-10) (Hot / Average / Cold)
3 / 2.5 / 3
Star Rating Heating
(0-10) (Hot / Average / Cold)
3 / 2.5 / 1.5
Total Cooling Seasonal Performance Factor Residential
kW (Hot / Average / Cold)
4.533 / 4.342 / 4.555
Heating Seasonal Performance Factor Residential
kW (Hot / Average / Cold)
4.521 / 4.001 / 3.428
Total Cooling Seasonal Performance Factor Commercial
kW (Hot / Average / Cold)
4.828 / 4.962 / 5.32
Heating Seasonal Performance Factor Commercial
kW (Hot / Average / Cold)
4.519 / 4.195 / 3.734
Running Current
amps (Cooling / Heating)
21.1 / 20.3
Moisture Removal
l/hr
3.4
Indoor Sound Pressure Cooling
dBA (High / Quiet)
44 / 39
Indoor Sound Pressure Heating
dBA (High / Quiet)
44 / 39
Outdoor Sound Pressure
dBA (Cooling / Heating)
53 / 55
Outdoor Sound Power
dBA
71
Static Pressure Range
PA (Min to Max)
60 to 250
Air Circulation (Indoor – High Fan) Cooling
l/sec
1139
Air Circulation (Indoor – High Fan) Heating
l/sec
1139
Indoor Unit Dimensions
mm (Height x Width x Depth)
360 x 1400 x 850
Indoor Unit Weight
kg
69.00
Outdoor Unit Dimensions
mm (Height x Width x Depth)
1418 x 970 x 370
Outdoor Unit Weight
kg
101.00
Piping Connects
mm Ø (Liquid / Gas)
9.52 / 15.88
Pipe Length
m (Max (Precharged))
75 (30)
Max Height Difference
m
30
Operation Range Cooling
°CDB (Min to Max)
-10 to 50
Operation Range Heating
°CDB (Min to Max)
-15 to 24
Refrigerant Type R32
Refrigerant Amount
g
3,800
View full details

Contact form